Abstract
In a study of the in vitro effectiveness of biocides against Legionella pneumophila, some aspects of the cooling tower environment were replicated in the laboratory, paying particular attention to water hardness and pH. Pieces of Douglas fir and polyvinyl chloride were colonized in a recirculating system and the comparative efficacy of two biocides (Bronopol and Kathon) against the sessile and planktonic populations was examined. While the biocides were relatively effective against the planktonic L. pneumophila population over a short period of time (minimum 9-12 h), substantially longer periods of time (maximum greater than 48 h) were required to reduce the number of cultivable bacteria to below detectable levels in the adherent population. The results indicate that failure to monitor the sessile population of L. pneumophila in laboratory studies of biocides may result in the use of incorrect dosages and/or contact times in field trials with apparently reduced in situ efficacy.Keywords
This publication has 41 references indexed in Scilit:
- Atypical legionellosis: Isolation of Legionella pneumophila serogroup 1 from a patient with aspiration pneumoniaJournal of Hospital Infection, 1989
- Resistance of bacterial biofilms to antibiotics a growth-rate related effect?Journal of Antimicrobial Chemotherapy, 1988
- ASSESSMENT AND CONTROL OF RISKS FROM LEGIONNAIRES' DISEASE *Annals of Occupational Hygiene, 1988
- Outbreak of Legionnaires' disease in Glasgow Royal Infirmary: microbiological aspectsEpidemiology and Infection, 1986
- Colonization of components of a model hot water system by Legionella pneumophilaJournal of Applied Bacteriology, 1985
- The Bacterial Glycocalyx in Nature and DiseaseAnnual Review of Microbiology, 1981
- An Outbreak of Legionnaires' Disease Associated with a Contaminated Air-Conditioning Cooling TowerNew England Journal of Medicine, 1980
- An Outbreak in 1965 of Severe Respiratory Illness Caused by the Legionnaires' Disease BacteriumThe Journal of Infectious Diseases, 1978
- Legionnaires' DiseaseNew England Journal of Medicine, 1977
- Ruthenium red and violet. I. Chemistry, purification, methods of use for electron microscopy and mechanism of actionThe Anatomical Record, 1971