Control of a dynamic brake to reduce turbine-generator shaft transient torques
- 1 January 1993
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Systems
- Vol. 8 (1) , 67-73
- https://doi.org/10.1109/59.221250
Abstract
A resistive, thyristor-controlled brake is used to damp transient torques in large thermoelectric generators supplying series-compensated transmission lines. Emphasis is placed on developing a suitable control algorithm and testing the algorithm through a wide variety of different operating configurations. Discrete-level generalized predictive control (GPC) is examined as one possible approach to optimal control of the brake. Some problems with implementation of GPC on the system are discussed. Prony analysis is used to identify system transfer functions, which are then related to control design considerations and robustness properties.>Keywords
This publication has 10 references indexed in Scilit:
- Third supplement to a bibliography for the study of subsynchronous resonance between rotating machines and power systemsIEEE Transactions on Power Systems, 1991
- Initial results in Prony analysis of power system response signalsIEEE Transactions on Power Systems, 1990
- Turbine-generator shaft oscillation monitoring with PCsIEEE Computer Applications in Power, 1989
- Torsional oscillations of unequally-loaded parallel identical turbine-generatorsIEEE Transactions on Power Systems, 1989
- Generalized predictive control—Part I. The basic algorithmAutomatica, 1987
- Second Benchmark Model for Computer Simulation of Subsynchronous ResonanceIEEE Transactions on Power Apparatus and Systems, 1985
- Damping Shaft Torsional Oscillations Using a Dynamically Controlled Resistor BankIEEE Transactions on Power Apparatus and Systems, 1981
- Turbine-Generator Shaft Torques and Fatigue: Part II - Impact of System Distribances and High Speed ReclosureIEEE Transactions on Power Apparatus and Systems, 1979
- Torsional Fatigue of Turbine-Generator Shafts Caused by Different Electrical System Faults and Switching OperationsIEEE Transactions on Power Apparatus and Systems, 1978
- Effect of clearing short circuits and automatic reclosing on torsional stress and life expenditure of turbine-generator shaftsIEEE Transactions on Power Apparatus and Systems, 1976