Indoor Air Quality Impacts of Ventilation Ducts: Ozone Removal and Emissions of Volatile Organic Compounds
- 1 October 1998
- journal article
- research article
- Published by Taylor & Francis in Journal of the Air & Waste Management Association
- Vol. 48 (10) , 941-952
- https://doi.org/10.1080/10473289.1998.10463740
Abstract
The concentrations of contaminants in the supply air of mechanically ventilated buildings may be altered by pollutant emissions from and interactions with duct materials. We measured the emission rate of volatile organic compounds (VOCs) and aldehydes from materials typically found in ventilation ducts. The emission rate of VOCs per exposed surface area of materials was found to be low for some duct liners, but high for duct sealing caulk and a neo-prene gasket. For a typical duct, the contribution to VOC concentrations is predicted to be only a few percent of common indoor levels. We exposed selected materials to ~100-ppb ozone and measured VOC emissions. Exposure to ozone increased the emission rates of aldehydes from a duct liner, duct sealing caulk, and neoprene gasket. The emission of aldehydes from these materials could increase indoor air concentrations by amounts that are as much as 20% of odor thresholds. We also measured the rate of ozone uptake on duct liners and galvanized sheet metal to predict how much ozone might be removed by a typical duct in ventilation systems. For exposure to a constant ozone mol fraction of 37 ppb, a lined duct would initially remove ~9% of the ozone, but over a period of 10 days the ozone removal efficiency would diminish to less than 4%. In an unlined duct, in which only galvanized sheet metal is exposed to the air-stream, the removal efficiency would be much lower, ~0.02%. Therefore, ducts in ventilation systems are unlikely to be a major sink for ozone.Keywords
This publication has 19 references indexed in Scilit:
- Evaluation of the Performance of DNPH-Coated Silica Gel and C18 Cartridges in the Measurement of Formaldehyde in the Presence and Absence of OzoneEnvironmental Science & Technology, 1998
- A Review and a Limited Comparison of Methods for Measuring Total Volatile Organic Compounds in Indoor AirIndoor Air, 1995
- Ozone in Residential Air: Concentrations, I/O Ratios, Indoor Chemistry, and ExposuresIndoor Air, 1994
- Removal of reactive gases at indoor surfaces: Combining mass transport and surface kineticsAtmospheric Environment. Part A. General Topics, 1993
- Indoor chemistry: ozone, volatile organic compounds, and carpetsEnvironmental Science & Technology, 1992
- A model for investigations of ventilation systems as sources for volatile organic compounds in indoor climateAtmospheric Environment. Part A. General Topics, 1991
- Consistent pattern of elevated symptoms in air-conditioned office buildings: a reanalysis of epidemiologic studies.American Journal of Public Health, 1990
- SICK BUILDING SYNDROME: A STUDY OF 4373 OFFICE WORKERSAnnals of Occupational Hygiene, 1987
- Determination of nanogram amounts of carbonyls as 2,4-dinitrophenylhydrazones by high-performance liquid chromatographyAnalytical Chemistry, 1981
- Concentrations, decay rates, and removal of ozone and their relation to establishing clean indoor airEnvironmental Science & Technology, 1973