Corona Studies for Biploar HVDC Transmission at Voltages Between ±600 kV and ±1200 kV Part 1: Long-Term Bipolar Line Studies
- 1 March 1981
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Apparatus and Systems
- Vol. PAS-100 (3) , 1453-1461
- https://doi.org/10.1109/tpas.1981.316620
Abstract
The corona performance characteristics of conductor bundles for use on transmission lines operating in the range of ±600 kV to ±1200 kV, obtained as part of a comprehensive corona study for transmission systems in this voltage range, are presented in this paper. The results presented in this paper complement those already published1 for a 4 x 1.6" conductor bundle chosen for a nominal voltage of ±750 kV. In addition to presenting the corona performance characteristics of 6 x 1.6" and 8 x 1.8" conductor bundles, corresponding to nominal voltages of ±900 kV and ±1050 kV respectively, the paper also presents a general analysis of some of the results obtained for all the three bundles tested. The study includes a detailed investigation of the important corona performance parameters, namely radio interference (RI), audible noise (AN) and corona losses (CL). Some measurements of ion current density and electric field at ground level are also presented.Keywords
This publication has 11 references indexed in Scilit:
- Corona Studies for Biploar HVDC Transmission at Voltages Between ±600 kV AND ±1200 kV PART 2: Special Biploar Line, Bipolar Cage and Bus StudiesIEEE Transactions on Power Apparatus and Systems, 1981
- Corona performance of a conductor bundle for bipolar HDVC transmission at plusminus 750 kVIEEE Transactions on Power Apparatus and Systems, 1977
- Conductor surface voltage gradients on bipolar HVDC transmission linesIEEE Transactions on Power Apparatus and Systems, 1976
- Contribution to the Electrical Design of EHVDC Overhead LinesIEEE Transactions on Power Apparatus and Systems, 1974
- Propagation Analysis of HF Currents and Voltages on Lossy Power LinesIEEE Transactions on Power Apparatus and Systems, 1973
- Comparison of Radio Noise Prediction Methods With CIGRE/IEEE Survey ResultsIEEE Transactions on Power Apparatus and Systems, 1973
- Test Line Experience with HVDC Overhead TransmissionIEEE Transactions on Power Apparatus and Systems, 1970
- Electrostatic Field of a System of Parallel Cylindrical ConductorsIEEE Transactions on Power Apparatus and Systems, 1969
- A Laboratory Study of the Effects of Wind on DC CoronaIEEE Transactions on Power Apparatus and Systems, 1967
- Corona Phenomena from Water Drops on Smooth Conductors under High Direct VoltageIEEE Transactions on Power Apparatus and Systems, 1965