Magnetic Field Induction From Overhead Transmission and Distribution Power Lines on Buried Irrigation Pipelines
- 1 March 1981
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Apparatus and Systems
- Vol. PAS-100 (3) , 990-1000
- https://doi.org/10.1109/TPAS.1981.316634
Abstract
Magnetic field induction from transmission and distribution power lines is discussed and shown to induce significant voltages on buried irrigation pipelines. Field tests are reported verifying that objectionable voltage levels can be induced on irrigation pipelines from distribution circuits during unbalanced conditions. Estimating curves are presented for transmission and sub-transmission power lines and mitigation methods are discussed as applied to irrigation pipelines for transmission and distribution power line interactionKeywords
This publication has 6 references indexed in Scilit:
- Mitigation of Buried Pipeline Voltages Due to 60 Hz AC Inductive Coupling Part II --Pipeline Grounding MethodsIEEE Transactions on Power Apparatus and Systems, 1979
- Mitigation of Buried Pipeline Voltages due to 60 Hz AC Inductive Coupling Part I-Design of Joint Rights-of-WayIEEE Transactions on Power Apparatus and Systems, 1979
- Prediction Method for Buried Pipeline Voltages Due to 60 Hz AC Inductive Coupling Part I-AnalysisIEEE Transactions on Power Apparatus and Systems, 1979
- Frequency of distribution arrester discharge currents due to direct strokesIEEE Transactions on Power Apparatus and Systems, 1976
- Electromagnetic Effects of Overhead Transmission Lines Practical Problems, Safeguards, and Methods of CalculationIEEE Transactions on Power Apparatus and Systems, 1974
- Electrostatic Effects OF Overhead Transmission Lines PART I-Hazards and EffectsIEEE Transactions on Power Apparatus and Systems, 1972