Negative Effect of High pH on Biocidal Efficacy of Copper and Silver Ions in Controlling Legionella pneumophila
Open Access
- 1 June 2002
- journal article
- Published by American Society for Microbiology in Applied and Environmental Microbiology
- Vol. 68 (6) , 2711-2715
- https://doi.org/10.1128/aem.68.6.2711-2715.2002
Abstract
Copper-silver (Cu-Ag) ionization has effectively controlled Legionella spp. in the hot water systems of numerous hospitals. However, it was ineffective at controlling Legionella in one Ohio hospital despite the confirmation of adequate total concentrations of copper and silver ions. The pH of the water at this hospital was found to be 8.5 to 9.0. The purpose of this study was to investigate the impact of pH and other water quality parameters, including alkalinity (HCO3−), hardness (Ca2+ and Mg2+), and amount of dissolved organic carbon (DOC), on the control of Legionella by Cu-Ag ionization. Initial concentrations of Legionella and copper and silver ions used in batch experiments were 3 × 106 CFU/ml and 0.4 and 0.08 mg/liter, respectively. Changes in bicarbonate ion concentration (50, 100, and 150 mg/liter), water hardness (Ca2+ at 50 and 100 mg/liter; Mg2+ at 40 and 80 mg/liter), and level of DOC (0.5 and 2 mg/liter) had no significant impact on the efficacy of copper and silver ions in killing Legionella at a neutral pH. When the pH was elevated to 9 in these experiments, copper ions achieved only a 10-fold reduction in the number of Legionella organisms in 24 h, compared to a millionfold decrease at pH 7.0. Silver ions were able to achieve a millionfold reduction in 24 h at all ranges of water quality parameters tested. Precipitation of insoluble copper complexes was observed at a pH above 6.0. These results suggest that pH may be an important factor in the efficacy of copper-silver ionization in controlling Legionella in water systems.Keywords
This publication has 12 references indexed in Scilit:
- Ionization Failure Not Due to ResistanceClinical Infectious Diseases, 2000
- Four Years of Experience with Silver-Copper Ionization for Control of Legionella in a German University Hospital Hot Water Plumbing SystemClinical Infectious Diseases, 1999
- Intermittent Use of Copper‐Silver Ionization for Legionella Control in Water Distribution Systems: A Potential Option in Buildings Housing Individuals at Low Risk of InfectionClinical Infectious Diseases, 1998
- Sustained transmission of nosocomial Legionnaires disease--Arizona and Ohio.1997
- Individual and combined effects of copper and silver ions on inactivation of Legionella pneumophilaWater Research, 1996
- Controlled Evaluation of Copper-Silver Ionization in Eradicating Legionella pneumophila from a Hospital Water Distribution SystemThe Journal of Infectious Diseases, 1994
- Bacterial interactions with silverBioMetals, 1990
- Efficacy of copper and silver ions and reduced levels of free chlorine in inactivation of Legionella pneumophilaApplied and Environmental Microbiology, 1989
- Influence of extracellular polysaccharides on the toxicity of copper and cadmium towardKlebsiella aerogenesMicrobial Ecology, 1977
- SALMONELLA TYPHIMURIUM RESISTANT TO SILVER NITRATE, CHLORAMPHENICOL, AND AMPICILLINThe Lancet, 1975