Electrical breakdown of mineral oil under non-uniform fields
- 21 October 1976
- journal article
- Published by IOP Publishing in Journal of Physics D: Applied Physics
- Vol. 9 (15) , 2287-2293
- https://doi.org/10.1088/0022-3727/9/15/020
Abstract
The dependence of the direct electrical breakdown voltage of degassed transformer oil and of gas-saturated oil on gap length for a point-sphere electrode system has been studied for the two polarities of the point. The effects of anodization of the sphere electrode on the breakdown voltage against gap characteristics have also been examined. The critical gap length at which the breakdown voltage is the same for both polarities of the point has been found to depend on the nature of the insulating film on the sphere electrode and on the type of gas dissolved in oil. The discussion of the results is based on the propagation of a corona discharge from the point electrode and the possibility of formation of a back streamer from the sphere electrode.Keywords
This publication has 11 references indexed in Scilit:
- Effect of Dissolved Gases, Stress, and Gap Spacing on High-Field Conductivity in Liquid InsulantsIEEE Transactions on Electrical Insulation, 1975
- Oxide films on arc cathodes and their emission and erosionJournal of Physics D: Applied Physics, 1975
- Corona discharges and bubbling in liquid nitrogenJournal of Physics D: Applied Physics, 1975
- Influence of an insulating film on the breakdown voltage of transformer oil in nonuniform fieldsProceedings of the Institution of Electrical Engineers, 1975
- Coronas in insulating liquidsJournal of Physics D: Applied Physics, 1974
- Prebreakdown events in liquid nitrogenJournal de Physique et le Radium, 1974
- Prebreakdown processes in electrically stressed insulating liquidsJournal of Physics D: Applied Physics, 1972
- Electrical discharges in liquid dielectricsJournal of Physics D: Applied Physics, 1971
- Liquid motion and internal pressure in electrically stressed insulating liquidsJournal of Physics D: Applied Physics, 1970
- Effect of organic additives on electrical breakdown in transformer oil and liquid paraffinProceedings of the Institution of Electrical Engineers, 1965