Factors Influencing the Insulation Coordination of Transformers
- 1 June 1933
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in Transactions of the American Institute of Electrical Engineers
- Vol. 52 (2) , 411-416
- https://doi.org/10.1109/T-AIEE.1933.5056326
Abstract
The following conclusions have been reached: 1. The time lag characteristics of major insulation are practically the same for both positive and negative waves. 2. The impulse ratio of major insulation is practically 2.2. 3. The present standard A.I.E.E. tests for the 34.5-kv class and above provide coordination with the proposed coordinating gaps. 4. A.I.E.E. tests below 34.5-kv class are too low and should be increased. 5. Greatest security is obtained if the surge flashover of the bushing is only slightly greater than that of the coordinating gap. A margin of 10 per cent is suggested as the most desirable bushing level.Keywords
This publication has 7 references indexed in Scilit:
- The Coordination of Transformer Insulation with Line InsulationTransactions of the American Institute of Electrical Engineers, 1932
- Surge-Proof TransformersTransactions of the American Institute of Electrical Engineers, 1932
- Lightning Investigation on Transmission Lines---IITransactions of the American Institute of Electrical Engineers, 1931
- Lightning Investigation on the 220-Kv. System of the Pennsylvania Power & Light Company (1930)Transactions of the American Institute of Electrical Engineers, 1931
- Lightning Investigation On the Appalachian Electric Power Company's Transmission SystemTransactions of the American Institute of Electrical Engineers, 1931
- Recommendations on Balancing Transformer and Line Insulations On Basis of Impulse Voltage StrengthTransactions of the American Institute of Electrical Engineers, 1930
- Symposium on Surge Voltage Investigations Surge Voltage Investigation on Transmission LinesTransactions of the American Institute of Electrical Engineers, 1928