By revisiting the air distribution and bioaerosol dispersion in Ward 8A where the largest nosocomial severe acute respiratory syndrome (SARS) outbreak occurred in Hong Kong in 2003, we found an interesting phenomenon. Although all the cubicles were in ‘positive pressure’ towards the corridor, the virus-containing bioaerosols generated from the index patient's cubicle were still transmitted to other cubicles, which cannot be explained in a traditional manner. A multi-zone model combining the two-way airflow effect was used to analyse this phenomenon. The multi-zone airflow model was evaluated by our experimental data. Comparing with the previous computational fluid dynamic simulation results, we found that the air exchange owing to the small temperature differences between cubicles played a major role in SARS transmission. Additionally, the validated multi-zone model combining the two-way airflow effect could simulate the pollutant transport with reasonable accuracy but much less computational time. A probable improvement in general ward design was also proposed.Keywords
This publication has 38 references indexed in Scilit:
- The effectiveness of an air cleaner in controlling droplet/aerosol particle dispersion emitted from a patient's mouth in the indoor environment of dental clinicsJournal of The Royal Society Interface, 2009
- Airborne transmission of disease in hospitalsJournal of The Royal Society Interface, 2009
- Movement of airborne contaminants in a hospital isolation roomJournal of The Royal Society Interface, 2009
- A schlieren optical study of the human cough with and without wearing masks for aerosol infection controlJournal of The Royal Society Interface, 2009
- Exhaled droplets due to talking and coughingJournal of The Royal Society Interface, 2009
- Personalized ventilation as a control measure for airborne transmissible disease spreadJournal of The Royal Society Interface, 2009
- Control of airborne infectious diseases in ventilated spacesJournal of The Royal Society Interface, 2009
- Reducing Risk of Airborne Transmitted Infection in Hospitals by Use of Hospital CurtainsIndoor and Built Environment, 2008
- Toward Understanding the Risk of Secondary Airborne Infection: Emission of Respirable PathogensJournal of Occupational and Environmental Hygiene, 2005
- Particle deposition indoors: a reviewIndoor Air, 2002