Transient Calculations on Crossbonded Cables
- 1 April 1983
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Apparatus and Systems
- Vol. PAS-102 (4) , 779-787
- https://doi.org/10.1109/tpas.1983.317940
Abstract
The present paper describes accurate and approximate methods of calculating transients on a crossbonded cable. Calculated results are compared with field test results, and the accuracy of the calculation, which has never been discussed in the previous publications, is proved. It is characteristic to a crossbonded cable that the sheath overvoltage is much greater than that on a noncrossbonded cable. This overvoltage is due to the reflection of a traveling-wave from the crossbonded points. The approximate method of a calculation shows satisfactory results with much smaller computation time in comparison with the accurate method if the number of crossbonding is large.Keywords
This publication has 4 references indexed in Scilit:
- Z-transform electromagnetic transient analysis of crossbonded cable transmission systemsIEE Proceedings C Generation, Transmission and Distribution, 1981
- Switching Overvoltages in Long Crossbonded Cable Systems Using the Fourier TransformIEEE Transactions on Power Apparatus and Systems, 1979
- Transient phenomena in crossbonded cable systems: analytical resultsProceedings of the Institution of Electrical Engineers, 1978
- Switching overvoltages in short crossbonded cable systems using the Fourier transformProceedings of the Institution of Electrical Engineers, 1975